Floor Framing
Building a floor that's strong and stiff: girders on posts, joists 16 inches on center sized from the UDC span tables, bearing of 1 1/2 inches on wood and 3 inches on concrete, joists doubled under parallel bearing walls, openings framed with doubled headers and trimmers, bridging, and subfloor. Wisconsin's notching and boring limits (1/6 depth, never in the middle third; holes 1/3 depth, 2 inches from edges), and why trusses and engineered joists follow the manufacturer.
- 5 min
- 6 steps
- 3 questions
- Lesson 9 of 111
In this lesson
- Girders and posts
- Joists
- Bearing
- Notching and boring
- Overhangs
- What to take from this
Picking up where you left off.
Girders and posts
In a basement house, the floor joists usually span from the foundation wall to a girder (beam) down the middle, carried by posts on their own footings 1. The UDC rules 2:
- Girders and beams are sized from the code’s tables or engineered.
- Built-up wood girders are fitted at posts, with joints tied together to carry horizontal loads, and fastened to the posts with framing anchors or clips. Deep beams (over 11 1/4 inches) need lateral restraint at columns, such as a saddle.
- Posts bear over the middle third of their footing, are restrained top and bottom, are positively attached to the beam, and have a steel bearing plate. An adjustable steel post’s screw must be cast in concrete or permanently disabled after it’s set.
Joists
Joists are chosen for strength and for stiffness, which limits bounce and cracking 1. The UDC’s span tables in SPS 325 Appendix A give the allowed span by size, spacing, species, and grade for the 40 psf floor live load 2. Spacing is most often 16 inches on center 1.
- Install joists crown up, with the biggest edge knots on top 1.
- Double joists where a bearing wall above runs parallel to them 2. Bearing partitions must sit over beams, girders, or other bearing walls, or within one joist depth of them unless the joists are designed for the load 2.
- Joists that meet over a girder overlap at least 3 inches and are nailed together with at least two 12d nails, or are butted and tied with straps, plates, or blocking 2. A joist’s tail may not run past the beam by more than its depth 2.
- Joists parallel to the foundation wall get blocking in the first space every 32 inches to brace the wall top 2.
Openings for stairs and chimneys are framed with doubled headers across the joist ends and doubled trimmers alongside, often hung in metal joist hangers 1.
Bridging, diagonal 1×3 cross-bridging or solid blocking, goes at midspan to stiffen the floor and spread concentrated loads, no more than 8 feet apart 1. Subfloor of plywood or OSB is glued and nailed over the top.
Quick check
Bearing partitions also have to sit over beams, girders, or other bearing walls.
Bearing
The ends of the framing need enough to sit on 2:
| Member | Minimum bearing |
|---|---|
| Sawn joist on wood or metal | 1 1/2 in. |
| Sawn joist on masonry or concrete | 3 in. |
| Beam or girder on its support | 3 in., full width of the beam |
| Engineered joists and beams | per the manufacturer |
Quick check
Girders and beams need at least 3 inches on their supports.
Notching and boring
Plumbers and electricians cut floor joists all the time. The limits 2:
- Notches in the top or bottom: no deeper than 1/6 of the joist depth, no longer than 1/3 of the depth, and never in the middle third of the span. End notches may be up to a quarter of the depth.
- Holes away from the edges: diameter no more than 1/3 of the joist depth, at least 2 inches from the top and bottom edges and from any other hole or notch. A hole within 2 inches of an edge counts as a notch.
- Beams and girders: no notching or boring at all without engineering.
- Trusses: never cut, bored, or notched 2. Engineered joists (I-joists, LVL) follow the manufacturer’s hole charts 2.
For a 2×10 (9 1/4 inches actual), that’s a notch of 1 1/2 inches at most near the ends and a hole of about 3 inches in the middle of the depth.
Quick check
Bore a hole in the middle of the joist instead, no bigger than 1/3 the depth and 2 inches from the edges.
Overhangs
A joist may cantilever beyond the wall below by no more than its own depth unless engineered, or up to 2 feet when it’s an extension of the main joists carrying only a wall and limited roof 2.
Playback is optional. If the player is unavailable, open the video at its source.
What to take from this
Joists 16 inches on center span from the foundation to a girder on posts that bear on the middle third of their footings. Size them from the span tables, install crown up, double them under parallel bearing walls, lap 3 inches over girders, and frame openings with doubled headers and trimmers. Give joists 1 1/2 inches of bearing on wood and 3 on concrete. Notch no more than 1/6 the depth and never mid-span; bore no more than 1/3 the depth, 2 inches from the edges; never cut trusses or beams.
Lesson complete
Nice work.
Sources for this lesson
- 1L. O. Anderson, O. C. Heyer. Wood-Frame House Construction (Agriculture Handbook No. 73). USDA Forest Service, Forest Products Laboratory. 1955. verifiedPublic domain handbook. Platform construction: the subfloor extends to the outside edges and walls are framed flat on it, raised, plumbed, braced, then capped with a second top plate lapping at corners; balloon framing runs studs from sill to rafter plate. Studs commonly 2x4 at 16 inches on center; framing lumber at no more than 19 percent moisture. Wood basement posts at least 6x6 on a pedestal; girders carry the inner ends of joists; joists usually 2-inch nominal, 6 to 12 inches deep, 16 inches on center, crown up, doubled under bearing partitions, lapped at girders; openings framed with doubled headers and trimmers; cross-bridging at midspan, no more than 8 feet apart; subfloor of boards or plywood; headers of two 2-inch members on edge over openings; diagonal or K bracing at corners; rafters erected in pairs after ceiling joists are fastened.
- 2Wis. Admin. Code ch. SPS 321, Uniform Dwelling Code: Construction Standards. Wisconsin Department of Safety and Professional Services. verifiedDesign loads (SPS 321.02): complete load path to the foundation; live loads 40 psf floors, 50 garage floors, 40 decks and porches, 20 ceilings with storage, 5 without; roof snow loads from the zone map, Zone 1 (north) 40 psf and Zone 2 (south) 30 psf; wind 20 psf horizontal and uplift or ASCE 7-05; span tables in SPS 325 Appendix A. Frost (321.16): footings and foundations, including stoops and landings, below frost penetration or at least 48 inches below grade, whichever is deeper, never on frozen material; exceptions for ASCE 32 frost-protected shallow foundations, areaways, and clean bedrock. Exits (321.03): two first-floor exit doors separated by the greater of 20 feet or a third of the floor's longest diagonal; egress windows at least 20 by 24 inches net clear opening, sill no more than 60 inches above the floor (a platform if over 46); basement sleeping rooms need a second exit. Ceilings at least 7 feet (321.06). Smoke alarms (321.09) in each sleeping room, outside sleeping areas within 21 feet, and on every level, hardwired and interconnected with battery backup.