Two-Prong Outlets and Ungrounded Circuits

Old houses are full of two-prong outlets on circuits with no ground wire. You can't just swap in a three-prong outlet and call it grounded, and you should never jumper the neutral to the ground screw. The code gives four honest choices: another two-prong outlet; a GFCI outlet marked "No Equipment Ground"; three-prong outlets downstream of a GFCI, each labeled; or running a real ground. Why a GFCI protects you even without a ground, and why a cheap plug-in tester can't catch the most dangerous mistake.

  • 4 min
  • 7 steps
  • 2 questions
  • Lesson 65 of 111

In this lesson

  1. The problem
  2. Four honest choices
  3. Why a GFCI works without a ground
  4. Never the bootleg ground
  5. Adding outlets is different
  6. Try it

Two-prong outlets are a hallmark of an old house, and so is the frustration of a three-prong plug with nowhere to go. The temptation is to buy a pack of three-prong outlets and swap them in. Don’t, at least not without one of the fixes below.

The problem

A three-prong outlet’s round hole connects to the equipment grounding conductor, a path that carries fault current back to the panel and trips the breaker if a hot wire touches a metal case. Old two-wire circuits, whether knob-and-tube or early cable, simply don’t have that wire. Wiring installed before about 1965 often didn’t require one 1. A three-prong outlet on such a circuit has a ground hole connected to nothing, which looks safe and isn’t.

Four honest choices

When the box has no grounding means, the code allows you to replace an outlet with 2:

  1. Another two-prong outlet. Like for like.
  2. A GFCI outlet, marked “No Equipment Ground.”
  3. Three-prong outlets supplied through a GFCI, either a GFCI outlet upstream on the same circuit or a GFCI breaker, with each outlet marked “GFCI Protected” and “No Equipment Ground.” (GFCI outlets come with these stickers.)
  4. A real ground: run an equipment grounding conductor to the box from an acceptable grounding point, and then install a normal grounded outlet 2.
Four cards with receptacle faces. One, two-prong for two-prong: like for like, simple and legal. Two, GFCI receptacle, with test and reset buttons: mark it 'No Equipment Ground.' Three, three-prong after a GFCI: mark each 'GFCI Protected' and 'No Equipment Ground.' Four, add a ground wire: run a grounding conductor to an approved point. Below left, a GFCI works without a ground: it compares current going out on the hot with current returning on the neutral and trips if some leaks away, through a person, for example; but new outlets added onto an old two-wire circuit must be properly grounded. Below right, never the bootleg ground: a receptacle with a red jumper from the neutral screw to the ground screw, crossed out; a plug-in tester says correct, but it can energize the metal case of whatever is plugged in.
Four legal fixes, and one dangerous shortcut. Credit: StudyCorner diagram after NEC 406.4(D) and EC&M · CC BY 4.0 · Source

One more rule: if you’re replacing an outlet in a place where GFCI protection is now required, like a kitchen counter, bathroom, or basement, the replacement must be GFCI protected regardless 2.

Why a GFCI works without a ground

A GFCI doesn’t need a ground wire to protect people. It constantly compares the current going out on the hot with the current coming back on the neutral. If some is missing, it’s leaking somewhere it shouldn’t, perhaps through you to the floor, and the GFCI shuts off in a fraction of a second. That’s why the code accepts it as the fix for two-wire circuits.

What a GFCI doesn’t provide is a grounding path for equipment that wants one, such as some electronics and surge protectors. Hence the “No Equipment Ground” label: it tells the next person the truth.

A practical trick: one GFCI outlet at the first outlet on the circuit can protect every outlet downstream if you connect them to its “load” terminals, so you can install ordinary three-prong outlets after it, each with the stickers.

Never the bootleg ground

The dangerous shortcut is the bootleg ground: installing a three-prong outlet and running a short jumper from the neutral screw to the ground screw. It’s a code violation that turns up more often than you’d think 1. And it’s sneaky: a cheap three-light plug-in tester, and even voltage readings between the slots, will often say the outlet is wired correctly 1. If the hot and neutral are also reversed somewhere upstream, the bootleg ground can energize the metal case of whatever’s plugged in 1.

If you buy an old house, look behind a few three-prong outlets on old circuits. A jumper from the silver screw to the green screw means that outlet needs to be fixed.

Quick check

Which of these is NOT a legal way to replace a two-prong outlet on a circuit with no ground?

Adding outlets is different

The GFCI option covers replacing existing outlets. If you extend an old two-wire circuit to add a new outlet, the new outlet must be the grounding type and actually grounded 2. The code’s logic is that it won’t make you rip out old wiring, but it won’t let you build onto it the old way either 2. In practice, a new outlet in an old house usually means a new circuit run in modern cable, which is the subject of the next lesson.

Does a GFCI Outlet Still Provide Protection Without A Ground Wire? Why a GFCI works without a ground. Credit: Everyday Home Repairs · YouTube standard license · 6:35 · Source

Playback is optional. If the player is unavailable, open the video at its source.

Quick check

Can you add a brand-new outlet off an old two-wire circuit and protect it with a GFCI instead of a ground?

Try it

Walk the house with a GFCI-equipped plug-in tester and a notepad. Note which outlets are two-prong, which are three-prong showing “open ground,” and which show correct. Then pick one circuit and plan the fix: a GFCI at the first outlet, with labels downstream, is often an afternoon’s work.

Lesson complete

Nice work.

1day streak
0/1today's goal
–correct

Up next · 4 min

Fishing New Cable Through Plaster Walls

Next lesson
Sources for this lesson
  1. 1
    Mike Sokol. Failures in Outlet Testing Exposed. EC&M (Electrical Construction & Maintenance). 2013. verifiedJuly 15, 2013. Pre-1965 wiring often has no equipment ground. A bootleg (false) ground is created when a grounded receptacle is installed on an ungrounded circuit and the ground screw is strapped to the neutral screw; a code violation that occurs more often than you'd think. A 3-light plug-in tester, and even voltage readings between hot, neutral, and ground, can show such outlets as correctly wired, especially the reverse-polarity bootleg ground, which can energize equipment chassis. Per NEC 250.130(C), add a proper equipment ground or use GFCI protection.
  2. 2
    Article 406: Receptacles. EC&M (Electrical Construction & Maintenance). verifiedReplacing a receptacle where the box has no grounding means (e.g., old 2-wire cable without a ground): use a nongrounding-type receptacle; or a GFCI receptacle marked 'No Equipment Ground'; or a grounding-type receptacle that is GFCI-protected and marked 'GFCI Protected' and 'No Equipment Ground.' A replacement in a location where GFCI protection is now required must be GFCI-protected (210.8). The GFCI option doesn't apply to new outlets extended from an existing ungrounded box: a branch-circuit extension must be grounding type and grounded per 250.130(C).