Building and Maintaining a House

Footings and Frost Depth

What a footing does (spreads the house's weight onto soil that can carry it) and the UDC's prescriptive sizes: continuous footings 8 inches deep and 4 inches wider than the wall on each side, pier footings 2 by 2 feet and 12 inches deep, on undisturbed soil bearing at least 2,000 psf, below frost or 48 inches. A worked bearing check, anchor bolts every 72 inches, and why a frost-free footing under a floating slab needs an isolation joint.

  • 5 min
  • 6 steps
  • 3 questions
  • Lesson 4 of 111

In this lesson

  1. Why footings are wide
  2. Prescriptive sizes
  3. What a footing sits on
  4. Frost depth
  5. Holding the house down
  6. What to take from this

Why footings are wide

A wall concentrates a house’s weight into a narrow line; soil can only carry so much per square foot. The footing spreads the load out. Wisconsin’s code says it plainly: the dwelling and attached structures (decks and garages included) must sit on a structural system that transmits and safely distributes the loads to the soil, and the footing’s bearing area has to be large enough that the soil’s bearing capacity isn’t exceeded 1.

Workers in hard hats setting steel rebar cages into a long trench dug for a concrete footing.
Setting rebar in a footing trench before the concrete pour. Credit: U.S. Army photo by Sgt. 1st Class andrew guffey · Public domain · Source

A quick check: suppose a bearing wall carries 2,400 pounds per running foot (roof snow, walls, floors, and the wall’s own weight), on soil good for 2,000 pounds per square foot. The footing needs 2,400 ÷ 2,000 = 1.2 feet of width, about 15 inches. Put the same wall on stiff clay (3,000 psf) and 0.8 feet would do.

The code’s presumed bearing values 1:

Soil psf
Wet soft clay, very loose silt, silty clay 2,000
Loose fine sand, medium clay, loose sandy clay 2,000
Stiff clay, firm inorganic silt 3,000
Firm sand, loose sandy gravel, firm sandy clay, hard dry clay 4,000
Dense sand and gravel, compact clay-sand-gravel 6,000
Rock 12,000

No footing may go on soil bearing less than 2,000 psf unless it’s engineered, and if a weaker layer lies under the soil the footing sits on, the weaker value governs 1.

A basement wall section: a continuous concrete footing 8 inches deep extending 4 inches each side of the wall, its bottom at least 48 inches below grade or below frost, on undisturbed or compacted soil; the wall topped by a sill plate on half-inch anchor bolts embedded 7 inches; panels showing a 2 by 2 foot, 12-inch-deep pier footing, chimney footing and anchor bolt spacing rules, and a table of presumed soil bearing values from 2,000 psf for soft clay to 12,000 psf for rock.
Wide enough for the soil, deep enough for frost. Credit: StudyCorner diagram after Wis. Admin. Code SPS 321.14-321.18 · CC BY 4.0 · Source

Quick check

A wall carries 2,400 pounds per running foot. On soil rated 2,000 psf, how wide must the footing be?

Prescriptive sizes

Unless designed by structural analysis, plain concrete footings follow these minimums 1:

  • Continuous (wall) footings: at least 4 inches wider than the wall on each side and 8 inches deep (nominal). Footings in unstable soil, soil that can’t stand vertically for the footing’s depth, must be formed.
  • Column or pier footings: at least 2 feet by 2 feet and 12 inches deep.
  • Trench footings, poured with the wall where the soil allows: at least 8 inches wide.
  • Chimney and fireplace footings: 4 inches beyond the masonry on each side, 12 inches deep.
  • Deck footings for attached decks or decks that serve as an exit: sized for the load and the soil, like the house’s.

So an 8-inch poured wall gets a footing at least 16 by 8 inches.

Quick check

Under the UDC’s prescriptive rules, how big must a continuous footing under an 8-inch foundation wall be?

What a footing sits on

Footings go on undisturbed or compacted soil free of organic material, or are reinforced to bridge poor spots 1. Never on topsoil, unprepared fill, organic soil, mud, or frozen ground 1. Don’t dig below a footing without shoring it.

Quick check

What may a footing never be placed on?

Frost depth

The bottom of every footing, stoops and landings included, goes below the frost penetration level or at least 48 inches below adjacent grade, whichever is deeper 1. The exceptions are frost-protected shallow foundations designed to ASCE 32, footings on clean bedrock, and the part of a foundation under a window areaway 1.

One trap: a structure on a floating slab (like an attached garage slab or a porch on a slab) may not be rigidly attached to a structure on frost footings unless there’s an isolation joint the full height between them 1. Otherwise frost heaves the slab, and it lifts or cracks whatever it’s tied to.

Holding the house down

The top of the foundation ties to the framing 1:

  • Anchor bolts at least 1/2 inch in diameter, embedded at least 7 inches in concrete or grouted masonry, no more than 72 inches apart and within 18 inches of each corner, each with a nut and washer tightened on the sill; or listed mechanical anchors, or an engineered system.
  • Where floor joists run parallel to the foundation wall, solid blocking in at least the first joist space every 32 inches, so the floor braces the top of the wall against soil pressure.
Forming House Footings Ep.29 Laying out and forming house footings. Credit: Essential Craftsman · YouTube standard license · 27:43 · Source

Playback is optional. If the player is unavailable, open the video at its source.

What to take from this

Footings spread the load so the soil isn’t overloaded: width = load per foot ÷ soil bearing, with 2,000 psf as the minimum soil without engineering. Prescriptively, wall footings are 8 inches deep and 4 inches wider than the wall on each side, pier footings 2 by 2 feet and 12 inches deep, all on undisturbed soil, below frost or 48 inches, never on frozen ground. Bolt the sill every 72 inches and within 18 of corners, and isolate floating slabs from frost-footed walls.

Lesson complete

Nice work.

1day streak
0/1today's goal
–correct

Up next · 5 min

Basements, Crawlspaces, and Slabs

Next lesson
Sources for this lesson
  1. 1
    Wis. Admin. Code ch. SPS 321, Uniform Dwelling Code: Construction Standards. Wisconsin Department of Safety and Professional Services. verifiedDesign loads (SPS 321.02): complete load path to the foundation; live loads 40 psf floors, 50 garage floors, 40 decks and porches, 20 ceilings with storage, 5 without; roof snow loads from the zone map, Zone 1 (north) 40 psf and Zone 2 (south) 30 psf; wind 20 psf horizontal and uplift or ASCE 7-05; span tables in SPS 325 Appendix A. Frost (321.16): footings and foundations, including stoops and landings, below frost penetration or at least 48 inches below grade, whichever is deeper, never on frozen material; exceptions for ASCE 32 frost-protected shallow foundations, areaways, and clean bedrock. Exits (321.03): two first-floor exit doors separated by the greater of 20 feet or a third of the floor's longest diagonal; egress windows at least 20 by 24 inches net clear opening, sill no more than 60 inches above the floor (a platform if over 46); basement sleeping rooms need a second exit. Ceilings at least 7 feet (321.06). Smoke alarms (321.09) in each sleeping room, outside sleeping areas within 21 feet, and on every level, hardwired and interconnected with battery backup.